The TAG®-5000 Phase-Free® Wireless Phaser provides a unique method of phasing across a single-phase or three-phase system to make certain that correct polarity has been established prior to "closing-in" a switch. The TAG-5000 consists of two units, a transmitter and receiver, which communicate via a radio frequency signal, thus eliminating the need for a connecting cord found on traditional phasing sets.  Since the units communicate via radio signals, the range of operation is extended to more than 33 feet through the air and over 1,000 feet along overhead conductors and can operate through walls or partitions.

The TAG-5000 can be used for all overhead and underground phasing applications with appropriate underground probes and is ideal for use at higher voltages – up to 230kv – where safety and ease-of-use are prime considerations.

In operation, the transmitter is placed in contact with an energized conductor. The transmitter first acts as a voltage detector by emitting audible and visual indications. After the voltage detection sequence, the transmitter then begins to transmit a signal to the receiver. The receiver is then placed in contact with another energized conductor. The receiver processes the signal and indicates if the conductors are "in" or "out-of-phase" by emitting both audible and visual alarms. The TAG-5000 design offers several advantages and increased safety over conventional phasing equipment such an extended range of operation - more than 33 feet through the air and up to 3,000 feet along overhead conductors.  The TAG-5000 has a lightweight design, can operate on voltages up to 230 kV and can easily be operated by one person.

Wireless Phasing Features

·         Range of operation is more than 33' through the air - over 1,000' along overhead conductors

·         No connecting cord between transmitter and receiver

·         Built-in universal splines for hotstick attachment

·         Rugged and lightweight design

·         Both transmitter and receiver powered by 9V lithium or alkaline battery

·         Audible and visual indications

·         All-Check™ self-test feature for verifying proper operation prior to use

·         Phase through walls and metal enclosures

·         Phase conductors on system voltages up to 230kV (phase-to-phase)

·         Includes overhead probes and foam filled carrying case

·         Can be used on 50Hz and 60Hz systems

HD Electric Company is committed to ongoing review and improvement of its product lines, and thus reserves the right to modify product design and specifications without notice.

以下中文資料介紹僅供參考,產(chǎn)品資料以英文為準(zhǔn)

TAG-5000數(shù)字高壓無(wú)線(xiàn)核相儀概述:

主要優(yōu)點(diǎn)在于去掉了連接開(kāi)路點(diǎn)兩端的引線(xiàn),使用起來(lái)比電壓表或核相器要簡(jiǎn)單。由于本儀器通過(guò)無(wú)線(xiàn)電信號(hào)來(lái)通訊,使用范圍可以擴(kuò)展到近10米,并且可以穿過(guò)圍墻和隔板使用。同時(shí),這種輕型的裝置(發(fā)射器和接收器每個(gè)的重量是1磅)提高了使用的舒適度,可以一個(gè)人輕松和安全地操作兩個(gè)儀器。TAG5000型的基本應(yīng)用是在困難的使用條件下,即現(xiàn)有的電壓表或核相器不適合使用的情況。在較高的電壓情況下,安全性和簡(jiǎn)易的使用是首要因素,TAG5000型是您理想的選擇。而且,這種裝置可以穿過(guò)圍墻和金屬屏蔽來(lái)使用,這在使用常規(guī)儀器時(shí)往往會(huì)面臨問(wèn)題。TAG5000型包括兩個(gè)部分。一個(gè)是電壓探測(cè)器和發(fā)射器的聯(lián)合裝置,首先判斷線(xiàn)路是否帶電,然后發(fā)出有關(guān)導(dǎo)體相位的信號(hào)。另一個(gè)是接收裝置,獲得發(fā)射器發(fā)出的信號(hào),然后在測(cè)試時(shí)用信號(hào)通知用戶(hù)導(dǎo)體達(dá)到了同相。在使用中,首先對(duì)所有線(xiàn)路使用TAG5000的發(fā)射器,裝置同線(xiàn)路進(jìn)行接觸,通過(guò)發(fā)出蜂鳴聲和閃爍光確定它們帶電。然后把發(fā)射器置于開(kāi)路點(diǎn)的一端,接收裝置依次置于開(kāi)路點(diǎn)另一端的各個(gè)導(dǎo)體上,直至找到與發(fā)射器所在的導(dǎo)體同相位的線(xiàn)路。

TAG-5000數(shù)字高壓無(wú)線(xiàn)核相儀操作方法:
1、先將 X和Y采集器分別掛到同一高壓線(xiàn)路上,主機(jī)顯示屏應(yīng)顯示X、Y同相。
2、在高壓線(xiàn)核相時(shí)應(yīng)分別將X和Y采集器按以下方法排列進(jìn)行核相:AA′同相000°左右,AB′不同相 120°左右,BB′ 同相000°左右, BC′不同相120°左右,CC′同相000°左右。
3、如果要得到JQ數(shù)值,應(yīng)將其中一采集器放到高壓線(xiàn)一采集點(diǎn)上不動(dòng),再將另一采集器圍繞高壓線(xiàn)另一采集點(diǎn)前后左右移動(dòng),以找出ZJQ的相位角度。 
4、在核相時(shí),如 AA′、AB′、BB′. BC′、CC′的測(cè)試數(shù)據(jù)均為顯示不同相,這是由于所測(cè)的兩組供電線(xiàn)路接線(xiàn)組別不同,可能會(huì)出現(xiàn)30或60°的相位差。下面介紹出現(xiàn)這種情況時(shí)的測(cè)量標(biāo)準(zhǔn)(以30°相位差為例):測(cè)試方法與①和②相同,所測(cè)結(jié)果以應(yīng)為:AA ' 不同相30°、AB'不同相120°,BB'不同相30°, BC'不同相120°、CC ' 不同相30°(注:120°和240°只表示正相序或逆相序) 
5、在測(cè)量≥10KV時(shí),X和Y可直接同時(shí)放在導(dǎo)線(xiàn)或絕緣皮上進(jìn)行核相 
6、在≥66KV核相時(shí),X和Y采集器可以采取接觸或非接觸方法核相。(如測(cè)量110KV和220KV時(shí),將X和Y采集頭放在高壓電線(xiàn)下方300mm至1000mm處。測(cè)量500KV時(shí),將X和Y采集頭放在高壓電線(xiàn)下方1000mm-2000mm處,測(cè)量左右允許偏差300mm) 
7、測(cè)相序。假設(shè)某條線(xiàn)為A相,將X放在A相上,Y放在另一相上,如顯示120°則說(shuō)明是順相序,該相應(yīng)為“B”,如顯示240°則是逆相序,該相應(yīng)為“C”。
8、驗(yàn)電。將其中一個(gè)采集器掛在高壓電線(xiàn)上,如主機(jī)屏幕顯示相應(yīng)采集器的符號(hào),則說(shuō)明該高壓線(xiàn)有電。相反,如主機(jī)屏幕不顯示該采集器的符號(hào),則說(shuō)明該高壓線(xiàn)無(wú)電。

TAG-5000數(shù)字高壓無(wú)線(xiàn)核相儀參數(shù):

1、電壓等級(jí) 400v~220Kv (標(biāo)配35KV)
2、無(wú)線(xiàn)傳送距離 20m
3、相位差測(cè)量精度 ±3度
4、頻率精度 ±1Hz
5、工作頻率 50Hz~60Hz
6、電源 9V電池
7、環(huán)境溫度 -20℃~+50℃
8、環(huán)境濕度 全天候
9、相位角范圍 相位角偏移小于±30°為同相
10、相位角偏移大于±30°為異相
11、校驗(yàn) 自動(dòng)校驗(yàn),也可在帶電導(dǎo)線(xiàn)上校驗(yàn)
12、重量 發(fā)射器0.52Kg、接收器0.2 Kg
13、尺寸 76×200mm
14、包裝 鋁合金箱

TAG-5000數(shù)字高壓無(wú)線(xiàn)核相儀特點(diǎn):

1、TAG5000數(shù)字高壓無(wú)線(xiàn)核相器屏幕顯示內(nèi)容:無(wú)線(xiàn)高壓核相儀,不同相、同相、頻率、X、Y、 。
2、電源:主機(jī)采用可充電電源,X 和 Y 采集器 5 節(jié) AG13 電池。
3、自動(dòng)關(guān)機(jī):開(kāi)機(jī)后8分鐘左右主機(jī)自動(dòng)關(guān)機(jī)
4、接觸被測(cè)強(qiáng)電場(chǎng)時(shí),儀器會(huì)自動(dòng)報(bào)警。

.無(wú)線(xiàn)電信號(hào)發(fā)送、接收和比較原理
·核相無(wú)導(dǎo)線(xiàn),更安全、方便
·高頻信號(hào)(433.9MHz)可以穿過(guò)圍墻、隔板和門(mén)等,適用性更廣
·當(dāng)場(chǎng)帶電校驗(yàn),更具KK性
·全天侯使用
·無(wú)線(xiàn)電波在空氣中傳送距離可達(dá)10米
·核相:聲光信號(hào)
·聚碳酸酯外殼,非常堅(jiān)固
·核相時(shí)一人操作、也可兩人操作
·重量:接收器(黃色):0.520kg;發(fā)射器(紅色):0.560kg
·TAG5000數(shù)字高壓無(wú)線(xiàn)核相器包括:發(fā)射器、接收器、探頭、儀器箱和說(shuō)明書(shū)。
用戶(hù)訂購(gòu)時(shí)須說(shuō)明電壓等級(jí):10kV、35kV、110kV、220kV(相電壓)